產品銷售、安裝、維修、保養檢測及消防安全評估
天(tian)津(jin)火災報警控制(zhi)器故(gu)障處理,主機報故(gu)障:故(gu)障燈亮,查(cha)看主機并消音(yin),若(ruo)是報警或聯(lian)動(dong)故(gu)障按下列(lie)操作:
1.做好當班(ban)記錄工作(zuo)。
2.若(ruo)外部電(dian)源正(zheng)常而主(zhu)(zhu)機(ji)依然報故障(zhang),由此出現的主(zhu)(zhu)電(dian)或備電(dian)故障(zhang)通(tong)知生產廠方技術人員進行維(wei)修處理,做好(hao)當班記錄工(gong)作(zuo)。
3.讀出故(gu)障(zhang)點的(de)地址(zhi)號(hao)及位(wei)置(zhi),后復位(wei)主機;若故(gu)障(zhang)依(yi)舊到(dao)現場查看線(xian)(xian)路是否(fou)斷(duan)線(xian)(xian)或短路(線(xian)(xian)路基準電壓26V~27.5V)。
4.電(dian)(dian)源(yuan)故(gu)(gu)障(zhang):查(cha)(cha)看是(shi)主電(dian)(dian)故(gu)(gu)障(zhang)還是(shi)備電(dian)(dian)故(gu)(gu)障(zhang)。主電(dian)(dian)故(gu)(gu)障(zhang):查(cha)(cha)看有無交(jiao)流(liu)220V電(dian)(dian)壓(ya)和主機內開關(guan)板(ban)上的保(bao)險管是(shi)否熔斷(duan)。備電(dian)(dian)故(gu)(gu)障(zhang):查(cha)(cha)看蓄(xu)電(dian)(dian)池(chi)有無直流(liu)24V電(dian)(dian)壓(ya)和開關(guan)板(ban)上的備電(dian)(dian)保(bao)險管是(shi)否熔斷(duan)。
5.線路正(zheng)常,故障依(yi)舊,通知生產廠(chang)方技術人員查看(kan)、處理(li)。
天津火災報警控制器廠家天津利安信合科技發展有限公司為您免費提供天津消防工程,天津消防工程檢測,天津消防工程公司等,歡迎致電咨詢。